FAdC Full LED Front Panel + RSR123 Diagnostics

FAdC Full LED Front Panel + RSR123 Diagnostics

RSR123 Diagnostic Table

ASD indication Voltmeter indication Meaning Possible measure(s)
< 4.75 mA / > 5.25 mA< 475 mV / > 525 mVRSR123 not adjustedAdjust RSR123
RSR123 mounted incorrectlyMount RSR123
RSR123 damped (traversed)Mount RSR123 correctly
< 3.75 mA / > 5.5 mAAlternating < 375 mV / > 550 mVRSR123 has dropped off the railCheck mounting, interrupt power, adjust again
Adjustment failedCheck mounting, interrupt power, adjust again
Occupancy detection failedCheck mounting, interrupt power, adjust again
Overcurrent detection failedCheck mounting, interrupt power, adjust again
RSR123 defectiveReplace RSR123
> 6 mA> 600 mVWire short-circuit (1↔2 or 3↔4)Rectify short-circuit
RSR123 connected incorrectlyConnect RSR123 correctly
0 mA0 mVWire break (1,2,3,4)Check cabling and connections
No RSR123 connectedConnect RSR123